Rectangular duct shoe tap flat pattern
A shoe tap, or shoe branch, takes a rectangular branch off the side of a main duct with a sloping heel, the shoe, so that the air turns into the branch smoothly. It is the standard take-off for a branch run in ventilation work, and is cut into the main duct's side on site or in the shop. This entry gives each cheek, the sloping shoe, the front and the back as its own cut file.
Make any size: download the 30-day free trial The Fabrication add-on
Two common sizes follow, each with its flat patterns as pictures, its cut files as DXF (and as DXF R12 for older cutting tables) and a 3D view to turn in your browser. Sizes are in millimetres, with inches beside them.
300 x 200 mm, 150 mm high, 100 mm shoe, 1 mm sheet
| Branch width, along the main duct | 300 mm (11.811 in) |
|---|---|
| Branch depth, across the main duct | 200 mm (7.874 in) |
| Branch height off the main duct's wall | 150 mm (5.906 in) |
| Shoe: how far upstream along the wall, and as high | 100 mm (3.937 in) |
| Plate thickness | 1 mm (0.039 in) |
| Seam allowance along the cheeks' joined edges | 0 mm (0 in) |
| Seam allowance along the other pieces' long edges | 0 mm (0 in) |
| Seam allowance at the branch's end and the shoe's joint | 0 mm (0 in) |
| Seam allowance along the edges on the main duct's wall | 0 mm (0 in) |
| Sizes measured on the | inside |
| Material | galvanised steel |
| Lock seam | none |
| End joint | plain |
| Flange height (formed flange) | 25 mm (0.984 in) |
Open the 3D view of this size (it needs JavaScript). Checked by folding the flat back up: within 0.001 mm of the 3D shape.
400 x 300 mm, 200 mm high, 100 mm shoe, 0.8 mm sheet
| Branch width, along the main duct | 400 mm (15.748 in) |
|---|---|
| Branch depth, across the main duct | 300 mm (11.811 in) |
| Branch height off the main duct's wall | 200 mm (7.874 in) |
| Shoe: how far upstream along the wall, and as high | 100 mm (3.937 in) |
| Plate thickness | 0.8 mm (0.031 in) |
| Seam allowance along the cheeks' joined edges | 0 mm (0 in) |
| Seam allowance along the other pieces' long edges | 0 mm (0 in) |
| Seam allowance at the branch's end and the shoe's joint | 0 mm (0 in) |
| Seam allowance along the edges on the main duct's wall | 0 mm (0 in) |
| Sizes measured on the | inside |
| Material | galvanised steel |
| Lock seam | none |
| End joint | plain |
| Flange height (formed flange) | 25 mm (0.984 in) |
Open the 3D view of this size (it needs JavaScript). Checked by folding the flat back up: within 0.001 mm of the 3D shape.
Your own sizes
These files are samples. With the Fabrication add-on you type your own sizes and thickness and get the flat patterns, the cut files and a marking table in seconds. It is free during the 30-day trial of DX-CAD.